Fire alarm maintenance guides
Every date here comes from the same rules as the planner. Pick the page closest to your question, then put your own dates into its planner.
Next service due 15 Dec 2026.
Any date from 15 Nov 2026 to 15 Jan 2027 is inside the 5 to 7 month window that BS 5839-1:2025 allows after the visit on 15 Jun 2026.
Service visits for the next two years
| Visit | Earliest | Due | Latest | Also at this visit |
|---|---|---|---|---|
| 1 | 15 Nov 2026 | 15 Dec 2026 | 15 Jan 2027 | ARC signals, panel clock, false alarm rate |
| 2 | 15 May 2027 | 15 Jun 2027 | 15 Jul 2027 | 12 months on: duct smoke detectors |
| 3 | 15 Nov 2027 | 15 Dec 2027 | 15 Jan 2028 | ARC signals, panel clock, false alarm rate |
| 4 | 15 May 2028 | 15 Jun 2028 | 15 Jul 2028 | 12 months on: duct smoke detectors |
Assumes each visit happens on its due date. If your last visit was not a 12-monthly one, the 12-monthly items fall on visits 1 and 3 instead. Every visit checks ARC signals, the panel clock and the false alarm rate.
Weekly call point rotation
With 12 call points, each one is operated once every 12 weeks, so about 4.3 times a year by the weekly test alone.
| Week | Date | Call point | Result | Signature |
|---|---|---|---|---|
| 1 | Mon 23 Nov 2026 | CP 1 | ||
| 2 | Mon 30 Nov 2026 | CP 2 | ||
| 3 | Mon 7 Dec 2026 | CP 3 | ||
| 4 | Mon 14 Dec 2026 | CP 4 | ||
| 5 | Mon 21 Dec 2026 | CP 5 | ||
| 6 | Mon 28 Dec 2026 | CP 6 | ||
| 7 | Mon 4 Jan 2027 | CP 7 | ||
| 8 | Mon 11 Jan 2027 | CP 8 | ||
| 9 | Mon 18 Jan 2027 | CP 9 | ||
| 10 | Mon 25 Jan 2027 | CP 10 | ||
| 11 | Mon 1 Feb 2027 | CP 11 | ||
| 12 | Mon 8 Feb 2027 | CP 12 |
False alarm rate
1 / 40 x 100 = 2.5 false alarms per 100 detectors per year. Under 4 per 100. The servicing engineer still checks the rate at every visit.
Runs in your browser; nothing you type is sent anywhere. England and Wales.
Testing and servicing guides
- How often a fire alarm should be serviced
- The weekly fire alarm test
- What goes in the fire alarm log book
- False alarm rate per 100 detectors
- When a fire alarm service is missed
- The 12 month fire alarm service
- Emergency lighting test schedule
Weekly call point rotation by system size
- Weekly test rotation for 6 call points
- Weekly test rotation for 12 call points
- Weekly test rotation for 24 call points
- Weekly test rotation for 60 call points
Reference
- BS 5839-1 fire alarm certificates
- What BS 5839-1:2025 changed for maintenance
- Fire alarm system categories
The law in England and Wales
Before you rely on these dates
- The rules here come from published summaries of BS 5839-1:2025 by the Fire Industry Association and the IET, and from fire and rescue service log book guidance, each linked on the page it is used. The standard itself is sold by BSI, so the wording on this site is ours.
- The planner works out dates, a rotation and a rate. It does not certify a system or replace a fire risk assessment.
- Your servicing company decides what each visit covers and issues the certificate. If their schedule differs, theirs is the one to follow.
- England and Wales. Scotland and Northern Ireland have their own fire safety law.