The weekly fire alarm test
BS 5839-1 puts the weekly test with the user of the building: the responsible person or someone they delegate it to. It proves the panel, the wiring to that call point and the sounders still work.
Next service due 15 Dec 2026.
Any date from 15 Nov 2026 to 15 Jan 2027 is inside the 5 to 7 month window that BS 5839-1:2025 allows after the visit on 15 Jun 2026.
Service visits for the next two years
| Visit | Earliest | Due | Latest | Also at this visit |
|---|---|---|---|---|
| 1 | 15 Nov 2026 | 15 Dec 2026 | 15 Jan 2027 | ARC signals, panel clock, false alarm rate |
| 2 | 15 May 2027 | 15 Jun 2027 | 15 Jul 2027 | 12 months on: duct smoke detectors |
| 3 | 15 Nov 2027 | 15 Dec 2027 | 15 Jan 2028 | ARC signals, panel clock, false alarm rate |
| 4 | 15 May 2028 | 15 Jun 2028 | 15 Jul 2028 | 12 months on: duct smoke detectors |
Assumes each visit happens on its due date. If your last visit was not a 12-monthly one, the 12-monthly items fall on visits 1 and 3 instead. Every visit checks ARC signals, the panel clock and the false alarm rate.
Weekly call point rotation
With 8 call points, each one is operated once every 8 weeks, so about 6.5 times a year by the weekly test alone.
| Week | Date | Call point | Result | Signature |
|---|---|---|---|---|
| 1 | Mon 23 Nov 2026 | CP 1 | ||
| 2 | Mon 30 Nov 2026 | CP 2 | ||
| 3 | Mon 7 Dec 2026 | CP 3 | ||
| 4 | Mon 14 Dec 2026 | CP 4 | ||
| 5 | Mon 21 Dec 2026 | CP 5 | ||
| 6 | Mon 28 Dec 2026 | CP 6 | ||
| 7 | Mon 4 Jan 2027 | CP 7 | ||
| 8 | Mon 11 Jan 2027 | CP 8 |
False alarm rate
1 / 40 x 100 = 2.5 false alarms per 100 detectors per year. Under 4 per 100. The servicing engineer still checks the rate at every visit.
Runs in your browser; nothing you type is sent anywhere. England and Wales.
Steps
- Operate one manual call point with its test key, during normal working hours.
- Check that the panel shows the alarm and that the alarm sounds.
- Reset the call point and the panel.
- Write the date, the zone, the call point used, the result and any fault in the log book, and sign it.
- Next week, use the next call point. Choose them on a strict rotation so every one gets used.
If the system sends signals to an alarm receiving centre, agree with the centre how test alarms are handled before you start.
The rotation for 8 call points starting on Monday 23 Nov 2026:
| Week | Date | Call point | Result | Signature |
|---|---|---|---|---|
| 1 | Mon 23 Nov 2026 | CP 1 | ||
| 2 | Mon 30 Nov 2026 | CP 2 | ||
| 3 | Mon 7 Dec 2026 | CP 3 | ||
| 4 | Mon 14 Dec 2026 | CP 4 | ||
| 5 | Mon 21 Dec 2026 | CP 5 | ||
| 6 | Mon 28 Dec 2026 | CP 6 | ||
| 7 | Mon 4 Jan 2027 | CP 7 | ||
| 8 | Mon 11 Jan 2027 | CP 8 |
Sources: South Wales Fire and Rescue Service log book, FireRegsPro, Hawthorne Systems. BS 5839-1 is sold by BSI and we have not reproduced it; the wording here is ours.
Who can do it, and what a contractor costs
The responsible person, or anyone they delegate it to. A contractor can do it too; one firm puts a weekly test visit at £45 to £90, which over 52 weeks costs far more than a few minutes of someone on site.
Before you rely on these dates
- The rules here come from published summaries of BS 5839-1:2025 by the Fire Industry Association and the IET, and from fire and rescue service log book guidance, each linked on the page it is used. The standard itself is sold by BSI, so the wording on this site is ours.
- The planner works out dates, a rotation and a rate. It does not certify a system or replace a fire risk assessment.
- Your servicing company decides what each visit covers and issues the certificate. If their schedule differs, theirs is the one to follow.
- England and Wales. Scotland and Northern Ireland have their own fire safety law.
Questions
Does the weekly test need an engineer?
No. BS 5839-1 places the weekly test with the user of the building. The six-monthly service is the engineer's job.
What if a call point fails?
Record the fault and the action taken in the log book and call the servicing company. Their name and number should be displayed at the main control panel.