Fire Alarm RegisterAll guides

BS 5839-1 fire alarm certificates

Each stage of a fire alarm system has a model certificate. The inspection and servicing certificate is the one a building sees after every service visit.

The date on the last servicing certificate, or the date a new system was accepted.
Every break glass point on the system.
The day the rotation starts. Same weekday each week.
Smoke, heat and multi-sensor heads. 0 for a manual system.
From the log book.

Next service due 1 Mar 2027.

Any date from 1 Feb 2027 to 1 Apr 2027 is inside the 5 to 7 month window that BS 5839-1:2025 allows after the visit on 1 Sep 2026.

Service visits for the next two years

VisitEarliestDueLatestAlso at this visit
11 Feb 20271 Mar 20271 Apr 2027ARC signals, panel clock, false alarm rate
21 Aug 20271 Sep 20271 Oct 202712 months on: duct smoke detectors
31 Feb 20281 Mar 20281 Apr 2028ARC signals, panel clock, false alarm rate
41 Aug 20281 Sep 20281 Oct 202812 months on: duct smoke detectors

Assumes each visit happens on its due date. If your last visit was not a 12-monthly one, the 12-monthly items fall on visits 1 and 3 instead. Every visit checks ARC signals, the panel clock and the false alarm rate.

Weekly call point rotation

With 12 call points, each one is operated once every 12 weeks, so about 4.3 times a year by the weekly test alone.

WeekDateCall pointResultSignature
1Mon 23 Nov 2026CP 1
2Mon 30 Nov 2026CP 2
3Mon 7 Dec 2026CP 3
4Mon 14 Dec 2026CP 4
5Mon 21 Dec 2026CP 5
6Mon 28 Dec 2026CP 6
7Mon 4 Jan 2027CP 7
8Mon 11 Jan 2027CP 8
9Mon 18 Jan 2027CP 9
10Mon 25 Jan 2027CP 10
11Mon 1 Feb 2027CP 11
12Mon 8 Feb 2027CP 12

False alarm rate

1 / 40 x 100 = 2.5 false alarms per 100 detectors per year. Under 4 per 100. The servicing engineer still checks the rate at every visit.

Runs in your browser; nothing you type is sent anywhere. England and Wales.

The certificates

ReferenceCertificateWhen
G1DesignBefore installation
G2InstallationWhen the wiring and devices are in
G3CommissioningWhen the system has been tested and works
G4AcceptanceWhen the user accepts it; the starting date for service periods
G5VerificationIn place of design, installation and commissioning
G6Inspection and servicingAfter every service visit
G7Modification; extension or modification from 2025After changes, including a panel firmware update

At the service the engineer records every defect and every departure from the standard, then issues the inspection and servicing certificate.

The G references come from FIA guidance written for an earlier edition, and the FIA notes certificates may not carry them. In the 2025 edition the model certificates are in Annex G.

Sources: FIA guidance on certificates, IET Wiring Matters, November 2025, FIA guide to the 2025 changes, Hawthorne Systems. BS 5839-1 is sold by BSI and we have not reproduced it; the wording here is ours.

Before you rely on these dates

Questions

Who issues the servicing certificate?

The competent person who services the system, after each visit.

Related

A service register for every site you look after

We are building a register for fire alarm engineers and building managers: every site's service dates and windows, weekly test rotations and false alarm rates in one place, with a reminder before a visit falls outside its window. Planned price £39 a month. Join the waitlist and we will email you when it opens. Nothing to pay now.