The rate is the false alarms in the last 12 months divided by the number of automatic detectors, times 100. The 2025 edition recommends checking the rate at every service visit.

The date on the last servicing certificate, or the date a new system was accepted.
Every break glass point on the system.
The day the rotation starts. Same weekday each week.
Smoke, heat and multi-sensor heads. 0 for a manual system.
From the log book.

Next service due 15 Dec 2026.

Any date from 15 Nov 2026 to 15 Jan 2027 is inside the 5 to 7 month window that BS 5839-1:2025 allows after the visit on 15 Jun 2026.

Service visits for the next two years

VisitEarliestDueLatestAlso at this visit
115 Nov 202615 Dec 202615 Jan 2027ARC signals, panel clock, false alarm rate
215 May 202715 Jun 202715 Jul 202712 months on: duct smoke detectors
315 Nov 202715 Dec 202715 Jan 2028ARC signals, panel clock, false alarm rate
415 May 202815 Jun 202815 Jul 202812 months on: duct smoke detectors

Assumes each visit happens on its due date. If your last visit was not a 12-monthly one, the 12-monthly items fall on visits 1 and 3 instead. Every visit checks ARC signals, the panel clock and the false alarm rate.

Weekly call point rotation

With 12 call points, each one is operated once every 12 weeks, so about 4.3 times a year by the weekly test alone.

WeekDateCall pointResultSignature
1Mon 23 Nov 2026CP 1
2Mon 30 Nov 2026CP 2
3Mon 7 Dec 2026CP 3
4Mon 14 Dec 2026CP 4
5Mon 21 Dec 2026CP 5
6Mon 28 Dec 2026CP 6
7Mon 4 Jan 2027CP 7
8Mon 11 Jan 2027CP 8
9Mon 18 Jan 2027CP 9
10Mon 25 Jan 2027CP 10
11Mon 1 Feb 2027CP 11
12Mon 8 Feb 2027CP 12

False alarm rate

3 / 60 x 100 = 5 false alarms per 100 detectors per year. At or over 4 per 100: the 2025 edition calls for a preliminary investigation.

Runs in your browser; nothing you type is sent anywhere. England and Wales.

Worked example

60 detectors and 3 false alarms in a year: 3 / 60 x 100 = 5 per 100 detectors per year. That is at or over 4, so a preliminary investigation is due. It is not over 5, so the in-depth level is not reached.

Thresholds

DetectorsFalse alarms in 12 monthsPer 100 detectors2025 investigation
2000None triggered
2015Preliminary
4025Preliminary
4037.5Preliminary
4124.88Preliminary
4137.32In-depth
10044Preliminary
10066In-depth
20094.5Preliminary
200115.5In-depth

Sources: FIA guide to the changes in BS 5839-1:2025. BS 5839-1 is sold by BSI and we have not reproduced it; the wording here is ours.

Recording false alarms

Each false alarm goes in the log book with its category, the date and time, and the cause if known.

Before you rely on these dates

Questions

Does a manual system have a rate?

The rate is per 100 automatic detectors, so a system with call points only has no rate to work out. False alarms still go in the log book.

Related

A service register for every site you look after

We are building a register for fire alarm engineers and building managers: every site's service dates and windows, weekly test rotations and false alarm rates in one place, with a reminder before a visit falls outside its window. Planned price £39 a month. Join the waitlist and we will email you when it opens. Nothing to pay now.